Long wire runs waste voltage as heat, leaving less for the load at the far end — dim lights and sluggish motors are the classic symptoms. Enter the current in amps, the one-way distance in feet and the copper wire gauge to see the drop.

The result is shown in volts and as a percentage of a 120V circuit. Electricians aim for under 3% on branch circuits and under 5% total.

How to use this calculator

Enter the current in amps, the one-way wire distance in feet, and pick the copper wire gauge. The calculator returns the voltage drop in volts, the percentage of a 120V circuit, and a verdict.

  1. Type the Current in amps the circuit will carry.
  2. Type the One-way distance in feet from panel to load.
  3. Pick the Wire gauge from the list.
  4. Read the drop in volts, the percentage, and the verdict.

Frequently asked questions

What does the Voltage Drop Calculator compute?

It estimates how many volts are lost as heat along a copper wire run. You enter current, one-way distance and wire gauge, and it returns the drop in volts, the drop as a percentage of a 120V circuit, and whether the result is acceptable.

What is the formula?

Voltage drop equals 2 times current times resistance per foot times one-way distance. The factor of 2 accounts for the round trip out and back along the pair of conductors.

Can you give a worked example?

20 amps over 100 feet of 12 AWG copper drops 6.35 volts, which is 5.3 percent of 120V, so the verdict is too high and a larger gauge is advised.

What percentage is acceptable?

Electricians generally aim for under 3 percent on branch circuits and under 5 percent total from service to load. Above 5 percent you should upsize the wire.